Ground Source Limited
Environmentally Friendly High Efficiency Heating & Cooling Systems
Home      Resources      Assessing Residential Viability
Print this pageAdd to Favorite

Assessing the Viability of a Residential Ground Source Heating and Cooling System

 

Ground Source systems have great flexibility and have been adopted in a wide range of applications. However, they are not a viable proposition for every project. The two main limitations with Ground Source systems are their land requirement for the loop field and the difficulties with retrofitting an appropriate heat distribution system within an existing building.

 

The following information has been prepared to provide interested parties with an indication of what is required in order to install a Ground Source system. Factors to consider in assessing the viability of a Ground Source system for a particular project include the heat distribution system to be adopted, the size and location of the ground source heat pump within the home and the type of loop field that can be installed. A summary of each factor is provided below to assist with assessing the viability of a Ground Source heating and cooling system for your project.

 

1. Selecting the Distribution System

Residential Ground Source systems can be operated either as air-ducted or hydronic slab (under-floor)  or radiator heating systems. The type of system installed is determined by the requirements of the home and personal preferences of the owner.

 

An air-ducted system utilises a water to air ground source heat pump and can be used for both heating and cooling. Hydronic (slab) heating utilises a water to water ground source heat pump and is typically only used for heating.

 

Retrofit projects should consider the viability of installing either ductwork or a hydronic pipe network. It may be worthwhile to discuss this with your builder or architect. Ground Source NZ is pleased to assist where possible.

2. The Ground Source Heat Pump

Ground Source is the New Zealand distributor for WaterFurnace, the worlds leading supplier of ground source heat pumps. WaterFurnace heat pumps have been incorporated into most Ground Source installations.

 

Capacity

The capacity of the ground source heat pump installed is directly related to the heating and cooling loads of the home. This is calculated by Ground Source and takes into account the size of the area to be heated, the location of the home and construction materials, including insulation, adopted.

 

We highly recommend that a professional peak demand heating and/or cooling demand is calculated for your building.
Construction materials, techniques and insulation values vary widely from building to building.
For example, a solar passive design home with 100 m2 to be heated could require a 2000 W or 2kW system, while a standard (H1) construction home requiring 80-100 w/m2 to be heated could require a 8-10,000 W or 8-10kW system.
The size of the system required can be reduced by zoning the home or considering measures such as additional insulation and/or double glazed windows.
 
The larger the system = higher capital installation cost and higher ongoing running costs
The reduced capital cost of a smaller ground source system will often more than cover cost increase of building energy improvements.


 

 

Physical Configuration

WaterFurnace manufacture both vertical and horizontal heat pumps, which is related to their physical configuration and not the type of loop field. Vertical units are typically located in a garage or a utility cupboard either within the home or on a covered verandah, while horizontal units are typically located within the roof space or beneath a bench or similar low feature. The physical configuration selected will depend on the location of the heat pump within the home. WaterFurnace also supply flexibility in the location of their air intakes and connections for ease of installation and access during any ongoing maintenance.

 

Refrigerant Gas

WaterFurnace ground source heat pumps supplied to the New Zealand market utilise ozone-safe R410A refrigerant.

Power Supply

It is recommended that WaterFurnace ground source heat pumps greater than approximately 7 kW are connected to a 3-phase 415 V power supply rather than the conventional single phase 240 V power supply. Most units greater than this capacity are only manufactured as 3-phase units. The reasoning is to limit drawdown on the local power supply at system start up. However it is possible to install single phase units greater than 10 kW capacity with the addition of soft start systems..

 

3. Selecting a Loop Field/Heat Exchanger

The loop field may be vertical, horizontal, closed water or open water. An open water loop may utilise either a surface water body or a groundwater aquifer as its heat exchanger. Loop field selection is primarily based on availability of land and/or availability of a water body.

 

Material used to construct the loop field is typically High Density Polyethylene (HDPE) which is filled with a solution of water and an anti-freeze solution and then pressurised to ensure the integrity of all seals. Exceptions include the use of plate heat exchangers in water bodies and open water loops.

 

Vertical Loops

Vertical loop fields are selected when there is insufficient space for a horizontal loop and a suitable water body is not available. This is typical of many urban blocks. The loop field typically consists of 3-6 boreholes drilled to depths of between 80 and 100 m. The boreholes must be at least 5 m apart and as such even vertical loop fields can at times require more space than is available. The loop is installed within the borehole which is then grouted to seal the hole and ensure good thermal contact with the surrounding rock. A vertical loop field can be installed in almost any geological conditions. One of the frequent limitations on a vertical loop field for retrofit project is the work area available for a drill rig. For example, a home may have a backyard suitable for a vertical loop field but if the drill rig can not gain access or established landscaping is present that can not be damaged then the systems may not be viable.

Due to the drill rig requirements, vertical loop fields are more expensive than the other loop field options. Typical cost is $7-13,000 per 100m bore hole

Horizontal Loops

Horizontal loops are installed in areas with additional land area but no suitable water body. The land area required must be sufficient to enable up to 300 m of trench to be excavated (for an 18 kW system). This may be in one long trench or a series of trench rows at least 3 m apart. Trenches are typically excavated to a depth of 2 m. Limitations on horizontal loops include shallow bedrock or rock outcrops and the presence of dry sand, which has poor thermal properties. There is good flexibility in the configuration of the trench and as such the occasional rock outcrop or tree is not of concern.

 

If a horizontal loop is difficult to fit on a site, it may be possible to utilise horizontal directional drilling to install the loop at greater depths. However, the cost of horizontal drilling increases the cost of loop field installation to that approaching a vertical loop. Otherwise, a horizontal loop field is almost half the cost of a vertical loop field.

 

Closed Water Loops

A closed water loop requires a body of water with sufficient depth and surface area to accommodate the heat exchange requirements of the loop. This may include a farm dam, pond, river, bay, harbour or the ocean. One of the difficulties of this is during the late summer or drought conditions when dams may become low or even dry. This tends to occur when the greatest cooling load is required on the system, resulting in a far from adequate co capacity. Any surface water body utilised to accommodate a closed water loop should be a minimum of 3 m deep at all times. The required surface area of the water body is based upon the heat load of the home and can be determined at the design stage. As a general rule, in an enclosed water body (ie dam or pond) 50 m2 of water surface is required per kilowatt of capacity.

 

The closed loop placed within the water body consists of either the same HDPE pipe used for vertical and horizontal loops or a plate heat exchanger constructed of stainless steel for freshwater applications or aluminium or titanium for sea water applications. Either construction method is less expensive than the earth-based loops.

 

Open Water Loops

Open water loops operate by flushing water through the heat pump and discharging it back into the environment. The water is not polluted in any way and as such does not cause a pollution concern.

A suitable water source is a groundwater aquifer or surface water body. Use of an aquifer will require an extraction well and a re-injection well, while a surface water body would require an inlet and an outlet. Discharged water may be slightly warmer or cooler than the intake water and as such the inlet and outlet should be at least 6 m apart depending on the available water source. Another alternative is to use discharge water for a second application such as irrigation or general water supply. Such alternatives will depend upon local regulations on groundwater use.

 

However, not all water bodies can be used for an open water loop. Water quality must meet minimum standards to ensure that excessive corrosion and scaling does not occur to the heat pump. This can be overcome with the use of sacrificial heat exchangers.

 

An open water loop is typically the most cost effective method of installing a Ground Source system. However, operational costs may be slightly higher than other loop fields due to the requirement to operate a pump to collect water and a higher level of preventative maintenance on the heat pump.

 

Alternative Loops

Alternative heat exchangers include treated effluent or other liquid streams which may be present at a site. Such alternatives tend to be limited on residential projects and should only be attempted after consultation with an experienced design engineer. In order to be considered feasible, it would be necessary for the liquid stream to be constantly present and be of minimum volume and flow rate in order to function effectively as a heat exchanger.

 

4. Residential Pools and Spas

The water to water ground source heat pumps used for hydronic heating can also be used to heat your pool or spa. A typical residential swimming pool may require a 25 kW unit while a spa, dependant on size may require anything from 3-30 kW unit. There is no difference with the loop field for a water heating unit.

 

One of the main considerations when designing your pool or spa is to realise that significant heat losses may occur overnight or if the water body is exposed to wind. It is therefore recommended that pool or spa covers be used overnight and when not in use.

 

4. Costs of a Ground Source System

Installation costs for a Ground Source system are typically more expensive than that of a conventional central air-conditioning system with approximately half the energy usage. In heating applications the energy usage could be 80% less than a conventional system. However, this will vary greatly depending on the source of heat, use of the system and the type of loop field installed. For example, bottled LPG systems are much more expensive to operate than conventional electrical systems while a vertical loop field is more expensive than a horizontal loop field.

 

The table provided below outlines budget estimates for a range of Ground Source systems. However, please note that these are provided as indicative only and are subject to a range of factors as discussed above. Their purpose is to provide prospective purchasers an indication of the capital costs likely to be encountered and for most projects will be an upper estimate. Remember that a standard construction home requires approximately 120 W per square meter of conditioned area and a well designed and constructed solar passive home may only require a little as 20 W per square meter of conditioned area.

 

Capacity (kW)

Approximate Budget Estimate for System with Vertical Loop Field

Approximate Budget Estimate for System with Horizontal Loop Field (trenching)

10

$35,000

$21,000-32,000

20

$59,000

$25,500- 42,000

30

$98 000

$36,000-48,000

40

$119 000

$46,000-58,000

Note 1: Costings provided are subject to detailed design and does not include the distribution system (ie hydronic piping or ducting).

Note 2: Costings for closed and open water loops not provided due to large discrepancies experienced for these projects. If you think that a water loop is suitable for your project please contact us and we can provide an estimate.

 

It should also be remembered that the value of Ground Source systems goes well beyond their capital cost. Ground Source systems have a design life in excess of 25 years, are very quiet and offer superior comfort levels.

 

5. Exploring Ground Source Further

We hope that the above information has enabled you to better understand the Ground Source concept by undertaking a self assessment of the viability of a Ground Source system for your project. If there are any outstanding questions or points requiring further clarification please do not hesitate to contact us.

 

If you would like Ground Source to undertake a detailed design and costing for your project please forward us a copy of your building plans and a site plan as well as information on construction materials, insulation and local soil and geological conditions. Electronic submission in pdf form is suitable. Ground Source can also provide a cost comparison with your choice of alternative options which will compare both installation and operating costs.

 

Ground Source can often provide a free system estimate, dependant on the amount of information supplied by the client. If your existing building designer, architect or engineer can supply the calculated peak heating/cooling demand this is an advantage.

For a full domestic or small scale commercial system design, Ground Source charges a non-refundable deposit of $450 + GST which is credited to the final project costs. The purpose of this charge is to cover the cost of design and calculations and to identify genuine enquiries. Note: peak heating/cooling demand calculations and modeling are additional if not supplied by the client.

 

We hope that the above has been useful in providing you with additional information on whether Ground Source is a viable solution for your project. If you have any questions or would like to discuss Ground Source further please do not hesitate to contact Ground Source. We would be very happy to discuss with you how Ground Source can be incorporated into your project.
 
 
This information is produced as a guide only. Although every effort has been made to ensure this information is accurate and up-to-date, Ground Source and/or its principals or representatives cannot be held responsible for errors, omissions or inaccuracies that maybe present.
©Ground Source Limited 2010